Skip to content

REM2 Class II enclosure

0,00  with VATPL

SKU: FIREBOX Category:

Application

For all switchgear requiring very high strength insulating material, providing full isolation and safety. The enclosure is applicable to the manufacture of switchgear:

  • RST – Transformer Station Switchgear,
  • SKS – HV Station Cable Cabinets,
  • SWS – WN Station Interior Cabinets,
  • ZK – Cable Connectors,
  • ZPP, ZPP-P, ZZP – Measurement sets,
  • SON – Street lighting cabinets,
  • TLP – Floor board switchboards,
  • RM – Modular Switchgear,
  • OU – Metal enclosures (OU-IP, OU-W, OU-RM, OU-SKS, OU-SIT, OU-S),
  • DU – Cover Doors.

Structure description

  • Outdoor standing on a concrete or metal foundation;
  • Internal standing on a metal pedestal or cable pocket;
  • Surface and recessed (plug-in) designs are possible, mounted on a special structure;
  • Made of aluminum or steel sheet joined by welding and bolting;
  • The thickness of the sheet metal adapted to the dimensions of the housing;
  • Can be achieved by an insulating layer, permanently lined on the inner and outer surfaces of the housing. The thickness of the layer ensures the right degree of insulation;
  • Insulation coating with high resistance to deterioration and external factors;
  • High resistance to UV, aging, weathering and aggressive chemical agents;
  • Long-term durability of the insulation coating;
  • IP30 to IP54 degree of protection;
  • Mechanical resistance: up to IK10;
  • Connecting to the foundation with insulation screws, and a special insulation spacer;
  • Isolated attachment of all mounting components from the housing body;
  • High mechanical strength at low and high temperatures;
  • The anti-allergenicity and harmlessness of the materials used in the production and insulation of the housing;
  • Easy to clean and remove dirt, anti-stain and anti-graffiti surface;
  • Doors of solid design;
  • Open to any side horizontally in single or double leaf versions;
  • Lockable with a basquil lock with a system cylinder and an additional padlock;
  • Additional gaskets installed in the door connection space provide additional tightness;
  • Three-point locking;
  • Adaptability of solutions to the applied apparatus, with the possibility of dividing into any number of parts – such as cable and measurement;
  • Separate enclosures for individual modules;
  • Single or gable roof with ventilation maze and double ventilation;
  • Preventing the accumulation of water and moisture;
  • The bottom has an opening to allow cables to enter from the cable duct.

Rated parameters

Rated switching voltage:230 V / 400 V
Rated insulation voltage:500 V / 690 V
Rated frequency:50 Hz
Surge voltage withstanding:8 kV
Rated-continuous current of the main rails:630A for ZK enclosures,
1250A for RST enclosures
Rated current of drain circuits:do 630 A
Rated short-term withstand current:20 kA
Rated peak withstand current:40 kA
Short-circuit current of the internal arc discharge:16 kA, 0,5 s
IP:standard 44
IK:10
Protection class:II
Flammability category:V0
UV Resistance:index 0

Download

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.